Description
MTL5082: Intrinsic Safety RTD Isolator Module
The MTL5082 is an easy-to-use, non-configurable isolator designed for use with 2-, 3-, or 4-wire RTD sensors in hazardous areas. It provides safe isolation and repeats the resistance signal to your monitoring system in the safe area. It is a perfect, simple alternative to a 4-20mA transmitter when a direct resistance output is needed. The module features open-circuit detection that drives the output upscale.
Technical Data
- Brand: MTL
- Model: MTL5082
- Input Resistance Range: 10 to 400 Ω
- Excitation Current: 200 μA
- Output Signal: Repeats Input Resistance (10 to 400 Ω)
- Open Circuit Fail-Safe: Upscale to 420 Ω
- Response Time: < 1s (to within 4%)
- Temperature Drift: ±10 mΩ/°C (typical)
- Power Supply: 20-35V DC
- Power Consumption: 45-65 mA
Installation Guide
- Connect your RTD sensor to the hazardous-area terminals.
- Terminal 1: RTD Input -ve
- Terminal 3: RTD Input +ve
- Terminal 4: 3-wire RTD Input -ve (compensation)
- Terminal 5: 4-wire RTD Input +ve (sense)
Connect your monitoring instrument to the safe-area output terminals (9, 10, 11, 12).
Apply power to terminals 13 (-ve) and 14 (+ve).
Use the switches on top to select the correct wiring mode (2, 3, or 4-wire) for your sensor.
Hazardous Area Certification: For use in Zone 0, IIC, T4 and Div 1, Group A areas.
Simple Apparatus: Terminals 1 & 3 meet the requirements for ‘simple apparatus’ (U ≤ 1.5V, I ≤ 0.1A, P ≤ 25mW).
Package Includes & Warranty
Your order includes: 1x MTL5082 Intrinsic Safety Isolator Module.
This product is covered by a 12-month warranty against defects in materials and workmanship.
Shipping
We ship worldwide via trusted carriers: FedEx, UPS, and DHL. Tracking information will be provided upon dispatch.











0.0 Average Rating Rated (0 Reviews)