MTL5043: HART-Enabled Hazardous Area Commander

Power smart transmitters in explosive zones! The MTL5043 safety barrier feeds dangerous-area sensors and sends dual signals to safe zones. HART communication on channel 1. Zone 0 certified.

???? Smart Features

  • Powers “smart” transmitters in explosive areas
  • Dual safe-zone output signals
  • HART digital communication
  • Auto fault detection

???? Performance Highlights

  • Input Range: 0-24mA (hazardous area)
  • Output Range: 4-24mA dual channels
  • Ch1 Load: 0-350Ω (0-130Ω for HART)
  • Ch2 Load: 0-550Ω active / 1kΩ passive
  • Accuracy: ±20μA (typically ±5μA)
  • HART Bandwidth: 400Hz-4kHz
  • Response: 500μs settling time
  • Isolation: 250V AC/DC protection
  • Voltage: 15.5V@20mA transmitter power

???? Power Connections

  • 1,2: Hazard Input (-/+)
  • 7: Ch2 Passive Output
  • 8,9: Ch2 Active Output (-/+)
  • 10,11,12: Ch1 Output (HART ready)
  • 13,14: DC Power (-/+)

????️ Secure Package

  • 12-month full coverage warranty
  • Priority shipping: Fedex, UPS, DHL
  • Green LED power monitor

???? Tech Talk

Q1: Does MTL5043 handle HART signals?
A: Yes! Channel 1 supports full HART communication.

Q2: What’s different about terminal 10?
A: Special 220Ω resistor for HART devices.

Q3: Can I use both output types on Ch2?
A: Yes! Choose active (terminals 8-9) or passive (terminal 7).

Q4: Which certifications support HART?
A: Look for Baseefa 03ATEX0584 marking.

Q5: How much power does it consume?
A: Only 1.7W max at 24V. Very efficient.

Additional information

Weight0.2 kg

0.0 Average Rating Rated (0 Reviews)

Rated
0%
Rated
0%
Rated
0%
Rated
0%
Rated
0%

Be the first to review “MTL HART Communication Isolator | Fast Delivery MTL5043”

Your email address will not be published. Required fields are marked *

You have to login to add images.